Constant Brightness Controller¶
- Knowledge Base
- Constant Brightness Controller
Function block for constant brightness control. Requires a well-positioned sensor that quickly detects the brightness in the room.
Table of Contents¶
- Inputs
- Outputs
- Parameters
- Properties
- Basic Programming
- Selecting and positioning the brightness sensor
Inputs↑¶
| Abbreviation | Summary | Description | Value Range |
|---|---|---|---|
| Br | Current brightness | ∞ | |
| Set | Sets output (Lc) to value of input (Set) | 0...100 | |
| Off | Off | Pulse: Outputs are reset / switched off. On: Block is locked. Dominating input. | 0/1 |
| Act | Activation | Activates constant brightness control when 1. | 0/1 |
Outputs↑¶
| Abbreviation | Summary | Description | Value Range |
|---|---|---|---|
| Lc | Light circuits | Supported are: Smart Actuator RGBW or WW, Lumitech, RGB, 0-100%, 0-10V, 1-10V. | ∞ |
| AC | API Connector | Intelligent API based connector. | - |
Parameters↑¶
| Abbreviation | Summary | Description | Unit | Value Range | Default Value |
|---|---|---|---|---|---|
| Hys | Hysteresis | If the difference between target and actual value is greater than this hysteresis, the controller will adjust. | % | 0...100 | 10 |
| Sts | Step size | The larger the step size, the quicker the target value is reached. However, large steps may cause the light change to be visible. | % | 0...100 | 5 |