Dimmer

Optimised dimmer with double click function for single button operation.

Table of Contents


Inputs

Abbreviation Summary Description Value Range
Tg Toggle Toggles output (D) between 0 and last value (or between 0 and 100 when parameter (Lv) is 1). Long-click for dimming up/down. 0/1
+ Dim+ Toggles output (D) between 0 and last value (or between 0 and 100 when parameter (Lv) is 1). Long-click for dimming up. 0/1
- Dim- Toggles output (D) between 0 and last value (or between 0 and 100 when parameter (Lv) is 1). Long-click for dimming down. 0/1
Off Off Pulse: Outputs are reset / switched off. On: Block is locked. Dominating input. The name of the connected sensor is used in the user interface. 0/1
DisPc Disable periphery control Disables inputs (Tg), (+), (-) when On. (e.g Child lock, cleaning) Control via user interface is still possible. 0/1
Set Sets output (D) to value of input (Set)

Outputs

Abbreviation Summary Description Value Range
D Dimmer output Analog output for dimmer control (e.g. 0-10V)
S Status On when output (D) is greater than 0. 0/1
AC API Connector Intelligent API based connector. -

Parameters

Abbreviation Summary Description Value Range Default Value
Rem Remanence input Remanence input: If active, the function block retains its previous state after a Miniserver reboot. 0/1 0
Di Delay input Delays input for set time. Applies to inputs (Tg), (+), (-). 0,4
Sts Step size 0,5
Str Step rate Dim value is in-/decreased by (Sts) every (Str) seconds on long-click. 0,2
MinD Minimum dim value 0
MaxD Maximum dim value 100
Dm Dim mode 1 = Dim between parameters (MinD) and (MaxD) on long-click. 0 = Stop dimming when reaching parameter (MinD) or parameter (MaxD) on long-click. Only applies to input (Tg). 0/1 0
Lv Last value 1 = Sets output (D) to (MaxD) when switching on. 0 = Sets last value to ouput (D) when switching on. 0/1 0

Presence Simulation

This function block has a presence simulation.