Energy Manager Gen. 1
With this function block, surplus energy, which is otherwise fed into the grid, can be used optimally. Up to 12 loads can be controlled.
Table of Contents
| Abbreviation |
Summary |
Description |
Unit |
Value Range |
| P |
Current power |
|
kW |
∞ |
| Ps |
Power energy storage |
Must be connected if output (Re) is used. |
kW |
∞ |
| Prio |
Priority selection |
Starts the selected load immediately. |
0/1 |
0...12 |
| L1-12 |
Start Load 1-12 |
|
- |
0/1 |
| Off |
Off |
Pulse: Outputs are reset / switched off. On: Block is locked. Dominating input. The name of the connected sensor is used in the user interface. |
- |
0/1 |
Outputs↑
| Abbreviation |
Summary |
Description |
Unit |
Value Range |
| L1-12 |
Load 1-12 |
|
- |
0/1 |
| Re |
Residual energy |
Can be used, for example, to charge a battery or a heating element (energy storage). If this output is used, the input (Ps) must be connected. |
kW |
∞ |
| AC |
API Connector |
Intelligent API based connector. |
- |
- |
Parameters↑
| Abbreviation |
Summary |
Description |
Unit |
Value Range |
Default Value |
| O |
Offset available energy |
Only so many consumers are activated that the current power (P) does not exceed this value. |
kW |
∞ |
0 |
Properties↑
| Summary |
Description |
Default Value |
| Properties |
Edit energy manager |
- |