Fire and Water Alarm
This function block will alert you of a fire or water leakage.
Table of Contents
| Abbreviation |
Summary |
Description |
Value Range |
| Ca |
Confirm alarm |
|
0/1 |
| Cs |
Confirm alarm signals |
Deativates outputs Pas and Mas. Outputs Pa and Ma remain active. Assigned Audio Players or Lighting Controllers are also switched off. |
0/1 |
| S |
Smoke detector |
Alarm input for external smoke detector. The name of the connected sensor is used in the user interface. |
0/1 |
| W |
Water detector |
Alarm input for external water detector. The name of the connected sensor is used in the user interface. |
0/1 |
| F |
AFCI |
Input for Arc-fault circuit interrupter. The name of the connected sensor is used in the user interface. |
0/1 |
| T |
Temperature input |
Connection for external temperature sensors. The name of the connected sensor is used in the user interface. |
∞ |
| Off |
Off |
Pulse: Outputs are reset / switched off. On: Block is locked. Dominating input. The name of the connected sensor is used in the user interface. |
0/1 |
Outputs↑
| Abbreviation |
Summary |
Description |
Value Range |
| Pa |
Pre-alarm |
|
0/1 |
| Ma |
Main alarm |
|
0/1 |
| Pas |
Pre-alarm signal |
|
0/1 |
| Mas |
Main alarm signal |
|
0/1 |
| N |
Number of active sensors |
|
∞ |
| At |
Alarm test |
|
0/1 |
| Ca |
Cause of alarm |
Reports cause of the last alarm. |
- |
| Ta |
Time and date of alarm |
Reports date and time of the last alarm. |
- |
| AC |
API Connector |
Intelligent API based connector. |
- |
Parameters↑
| Abbreviation |
Summary |
Description |
Unit |
Value Range |
Default Value |
| Rem |
Remanence input |
Remanence input: If active, the function block retains its previous state after a Miniserver reboot. |
- |
0/1 |
0 |
| Mad |
Main alarm delay |
Main alarm delay after activating the pre-alarm. |
s |
0...∞ |
120 |
| Maxϑ |
Maximum temperature |
If input (T) exceeds this value, the alarm will be activated. |
° |
∞ |
43 |
| MaxA |
Maximum alarm duration |
The main alarm is automatically confirmed at the end of set time. If (Pac) = 1, the pre-alarm is also automatically confirmed. 0 = No duration limit |
s |
0...∞ |
300 |
| Pac |
Pre-alarm confirmation |
1 = Pre-alarm is confirmed automatically when (MaxA) is reached. 0 = Pre-alarm stays active when (MaxA) is reached. |
- |
0/1 |
0 |
| Sm |
Service mode |
Enables the Service mode and suppresses the alarm, only (At) is activated in case of an alarm. 0 = Service mode off, 1 = Service mode permanently on, >1 = Service mode on for this time. |
s |
0...∞ |
0 |
Properties↑
| Summary |
Description |
Value Range |
Default Value |
| Number of messages |
Maximum number of saved messages. |
2...100 |
- |
| Configuration |
Configuration of the available inputs and outputs. |
- |
- |
Application↑
Loxone products, such as the Smoke Detector Air and Water Sensor Air, can simply be selected in the configuration dialog (double-click on block).