Meter & Storage
This meter is used to integrate a storage and records its level, charging and discharging.
The values are retrieved from a physical utility meter or from the storage itself.
In combination with other meter function blocks, various consumers, producers or storages can be linked via the Energy Flow Monitor for an overall view.
Table of Contents
| Abbreviation |
Summary |
Description |
Value Range |
| Pf |
Power or flow |
If only this input is used, the meter reading is also calculated from it. Otherwise it is only used for the output (Pf) and the user interface. |
∞ |
| Mrd |
Meter reading Discharge |
Discharge Input for meters that send the meter reading directly as an analog value. For meters that only send partial quantities (e.g. Smart Socket), relative metering must be activated in the settings of the block. |
0...∞ |
| Mrc |
Meter reading Charge |
Charge Input for meters that send the meter reading directly as an analog value. For meters that only send partial quantities (e.g. Smart Socket), relative metering must be activated in the settings of the block. |
0...∞ |
| Slvl |
Storage level or state of charge |
|
∞ |
| R |
Reset |
Pulse: Meter reading outputs are reset. On: Block is locked. |
0/1 |
Outputs↑
| Abbreviation |
Summary |
Description |
Value Range |
| Pf |
Power or flow |
Positive value: Storage is being discharged. |
∞ |
| Mrd |
Meter Reading discharge |
|
0...∞ |
| Rdd |
Reading today discharge |
|
0...∞ |
| Rldd |
Reading yesterday discharge |
|
0...∞ |
| Rmd |
Reading this month discharge |
|
0...∞ |
| Rlmd |
Reading last month discharge |
|
0...∞ |
| Ryd |
Reading this year discharge |
|
0...∞ |
| Rlyd |
Reading last year discharge |
|
0...∞ |
| Mrc |
Meter Reading charge |
|
0...∞ |
| Rdc |
Reading today charge |
|
0...∞ |
| Rldc |
Reading yesterday charge |
|
0...∞ |
| Rmc |
Reading this month charge |
|
0...∞ |
| Rlmc |
Reading last month charge |
|
0...∞ |
| Ryc |
Reading this year charge |
|
0...∞ |
| Rlyc |
Reading last year charge |
|
0...∞ |
| Slvl |
Storage level or state of charge |
|
∞ |
| AC |
API Connector |
Intelligent API based connector. |
- |
Parameters↑
| Abbreviation |
Summary |
Description |
Value Range |
Default Value |
| Mrod |
Meter reading offset discharge |
Value is added to output (Mrc). |
∞ |
0 |
| Mroc |
Meter reading offset charge |
Value is added to output (Mrd). |
∞ |
0 |
Properties↑
| Summary |
Description |
Value Range |
Default Value |
| Power/Flow direction |
Specifies whether the physical meter provides the charge or discharge value as a positive or negative value to the Pf input of the block. |
- |
- |
| Maximum storage level |
Maximum storage level used for the user interface |
0...∞ |
100 |
| Relative metering |
Active: The physical meter only sends partial quantities at intervals (relative), the block adds them up and uses them to form the meter reading. |
- |
- |
| Report invalid Meter Reading |