Network Intercommunication

Network Intercommunication allows data to be exchanged between Miniservers that are connected to a network via their Ethernet interface but are programmed independently of each other.

Digital values, analog values and text can be sent, with optional encrypted transmission (AES-128-CBC).

The transmission capacity of the network intercommunication is limited to an average value of 35 messages per second over a period of 2 minutes. If this is exceeded, secure transmission is no longer guaranteed and a system message appears.

Table of Contents


Properties

Summary Description Value Range Default Value
Own ID ID with which the own Miniserver can be uniquely identified by other Remote Systems. Maximum length: 8 characters - -
Port UDP port on which packets are received. This port must also be set in the properties of the Remote System on the sending Miniserver. 1000...65535 61263