Network Intercommunication¶
- Knowledge Base
- Network Intercommunication
Network Intercommunication allows data to be exchanged between Miniservers that are connected to a network via their Ethernet interface but are programmed independently of each other.
Digital values, analog values and text can be sent, with optional encrypted transmission (AES-128-CBC).
The transmission capacity of the network intercommunication is limited to an average value of 35 messages per second over a period of 2 minutes. If this is exceeded, secure transmission is no longer guaranteed and a system message appears.
Table of Contents¶
Properties↑¶
| Summary | Description | Value Range | Default Value |
|---|---|---|---|
| Own ID | ID with which the own Miniserver can be uniquely identified by other Remote Systems. Maximum length: 8 characters | - | - |
| Port | UDP port on which packets are received. This port must also be set in the properties of the Remote System on the sending Miniserver. | 1000...65535 | 61263 |