Up to 16 radio buttons, only one output can be active at a time. For example, pulse at input (I3) activates (O3).
Table of Contents
| Abbreviation |
Summary |
Description |
Value Range |
| I1-16 |
Input 1-16 |
Switches the respective output 1-16 On. |
0/1 |
| + |
Next output |
|
0/1 |
| - |
Previous output |
|
0/1 |
| Sel |
Select output |
Switches to specific output. |
0...16 |
| Off |
Off |
Pulse: Outputs are reset / switched off. On: Block is locked. Dominating input. The name of the connected sensor is used in the user interface. |
0/1 |
| DisPc |
Disable periphery control |
Disables all inputs when On. (e.g Child lock, cleaning) Control via user interface is still possible. |
0/1 |
Outputs↑
| Abbreviation |
Summary |
Description |
Value Range |
| O1-16 |
Output 1-16 |
|
0/1 |
| N |
Number of active output |
|
0...16 |
| AC |
API Connector |
Intelligent API based connector. |
- |
Parameters↑
| Abbreviation |
Summary |
Description |
Value Range |
Default Value |
| Rem |
Remanence input |
Remanence input: If active, the function block retains its previous state after a Miniserver reboot. |
0/1 |
0 |
| Max |
Max. outputs |
Maximum number of selectable outputs. Example: Max=4 -> only outputs 1-4 can be activated via block inputs. In the user interface, all labeled outputs can be activated regardless of this setting. |
1...16 |
4 |
| Sk0 |
Skip 0 |
'All-off' (0) is skipped when switching with +/- when On. Applies only to object inputs, not to the buttons in the user interface. |
0/1 |
0 |
Properties↑
| Summary |
Description |
Default Value |
| Edit outputs |
Edit output names |
- |
Labelling Outputs↑
Outputs can be labeled by double-clicking on the block.