Window

Controls a window.

Table of Contents


Inputs

Abbreviation Summary Description Unit Value Range
Co Complete open If in motion, stops. - 0/1
Cc Complete close If in motion, stops. - 0/1
Tg Toggle Toggles between open, stop, close. For single button control. - 0/1
Pos Position of window Move window to specified position. % 0...100
Po Partial open with push & hold - 0/1
Pc Partial close with push & hold - 0/1
Wp Weather protection Window is closed and locked for further operation when on. Control via user interface is still possible. - 0/1
Off Off Pulse stops movement. On locks the block. Dominating input. The name of the connected sensor is used in the user interface. - 0/1
Io Is open Input is used to report the “fully opened” position via a limit switch or similar. - 0/1
Ic Is closed Input is used to report the “fully closed” position via a limit switch or similar. - 0/1
CPos Current position Input indicating the current tilt position or opening width of the window. % 0...100
So Slightly Open Moves window to slightly open position if current position is different. - 0/1

Outputs

Abbreviation Summary Description Unit Value Range
Op Open - 0/1
Cl Close - 0/1
Pos Position of Window Position of the window (0.0 = closed, 1.0 = open) - 0...1
TPos Target position Output for target tilt position or target opening width (Schüco). % 0...100
AC API Connector Intelligent API based connector. API Commands - -

Parameters

Abbreviation Summary Description Unit Value Range Default Value
Opd Opening duration s 0...∞ 5
Cld Closing duration s 0...∞ 5
minTd Minimum travel time Minimum travel time at pulse on input (Po) or (Pc). s 0...∞ 0,4
Mld Motor lock duration Duration of motor lock between direction changes s 0...∞ 0,5
SoPos Slightly Open Position Target position for input So % 0...100 50

Properties

Summary Description Value Range Default Value
History Entries Number of entries in the control history. 0...100 20